SIVACON 8PS TRUNKING SYSTEMS
BD01 system
Safe, demand-oriented power supply
The BD01 system is designed for applica- tions from 40 A to 160 A. It is employed in trade and industry enterprises to safely supply small consumers with power,
or to realise the infeed of a lighting system. Planning is especially simple and it ensures a flexible power supply. In addition to the pre-wired tap-off units, which can also be individually equipped with components, numerous add-on devices such as protection devices or combinations with SCHUKO or CEE socket outlets are available. Tap-off units up to 63 A that can be plugged on/off while energised1) enable quick and easy modification or expansion of the power distribution.
Guided mounting and clear load assignment
The reliable mechanical and electrical connection technology ensures error-free installation thanks to the asymmetry
of the connection point of the BD01 system.
The codable tap-off points and units
can be clearly assigned to the loads.
The operating personnel are afforded
a high degree of protection by the guided mounting of the tap-off units. The tap-off points are only automatically opened upon connection of the tap-off units. As soon
as these units are removed, the tap-off points close automatically.
Simple planning of a modern network structure
The tap-off units can be plugged onto
all system sizes. Feeding units can be used as incoming, end, or center feeding unit. These two facts make both planning and stock keeping easier. Numerous components are available, so that power supply can be flexibly adapted to all building structures using 3D junction units.
Ancillary equipment units for increased functionality
Feeding unit attachable to any connection point
Technical data
Busbar coating | Epoxy | 19 | ||||||
Insulation | Air-insulated | 18 | ||||||
Mounting Position | Vertical, horizontal | 17 | ||||||
Standards | IEC 61439-1/-6 | IEC 61439-1/-6 | 16 | |||||
Housing material | Galvanised and painted sheet steel | - | 15 | |||||
Conductor material | Aluminium or copper | Aluminium | 14 | |||||
Connection technology | Connecting flanges with integrated expansion compensation | Single-bolt clamped connection with hook and bolt connection | 13 | |||||
Data transmission | Data cable | - | 12 | |||||
Tap-off unit | Up to 63 A | - | 11 | |||||
Tap-off point | Either 0.5 m or 1 m on one side | - | 10 | |||||
Fire load (per tap-off point) | '- | - | 9 | |||||
Fire load | Max. 0.76 kWh/m | Depending on the application | 8 | |||||
Number of conductors | 4 (PE = housing) | 3 to 9 conductors | 7 | |||||
Rated short-time withstand current Icw (1s) | Up to 2.5 kA | 50 kA | 6 | |||||
Rated peak withstand current Ipk | Up to 15.3 kA | 105 kA | 5 | |||||
Rated current InA | 40 A to 160 A | 1,800 A to 7,000 A | 4 | |||||
Degree of protection | IP54, IP55 | IP00 | 3 | |||||
Rated operational voltage Ue | 400 V AC | 1,000 V AC | 2 | |||||
Rated insulation voltage Ui | 400 V AC | 1,000 V AC | 1 |
התועלת שלך
בטיחות לאנשים ולצמחים
באמצעות אימות תכנון עם בדיקות לפי
IEC 61439-2
בטיחות אישית ומפעל במקרה של קשתות באמצעות בדיקות לפי IEC/TR 61641
גמישות גבוהה הודות לעיצוב מודולרי חדשני