top of page

SIVACON 8PS TRUNKING SYSTEMS
BD01 system

BD01_0.png

Safe, demand-oriented power supply

The BD01 system is designed for applica- tions from 40 A to 160 A. It is employed in trade and industry enterprises to safely supply small consumers with power,

or to realise the infeed of a lighting system. Planning is especially simple and it ensures a flexible power supply. In addition to the pre-wired tap-off units, which can also be individually equipped with components, numerous add-on devices such as protection devices or combinations with SCHUKO or CEE socket outlets are available. Tap-off units up to 63 A that can be plugged on/off while energised1) enable quick and easy modification or expansion of the power distribution.

Guided mounting and clear load assignment

The reliable mechanical and electrical connection technology ensures error-free installation thanks to the asymmetry
of the connection point of the BD01 system.

The codable tap-off points and units
can be clearly assigned to the loads.
The operating personnel are afforded
a high degree of protection by the guided mounting of the tap-off units. The tap-off points are only automatically opened upon connection of the tap-off units. As soon

as these units are removed, the tap-off points close automatically.

Simple planning of a modern network structure

The tap-off units can be plugged onto
all system sizes. Feeding units can be used as incoming, end, or center feeding unit. These two facts make both planning and stock keeping easier. Numerous components are available, so that power supply can be flexibly adapted to all building structures using 3D junction units.

BD01_1.jpg

Ancillary equipment units for increased functionality

BD01_2.jpg

Feeding unit attachable to any connection point

BD01_3.jpg

Technical data

Busbar coating
Epoxy
19
Insulation
Air-insulated
18
Mounting Position
Vertical, horizontal
17
Standards
IEC 61439-1/-6
IEC 61439-1/-6
16
Housing material
Galvanised and painted sheet steel
-
15
Conductor material
Aluminium or copper
Aluminium
14
Connection technology
Connecting flanges with integrated expansion compensation
Single-bolt clamped connection with hook and bolt connection
13
Data transmission
Data cable
-
12
Tap-off unit
Up to 63 A
-
11
Tap-off point
Either 0.5 m or 1 m on one side
-
10
Fire load (per tap-off point)
'-
-
9
Fire load
Max. 0.76 kWh/m
Depending on the application
8
Number of conductors
4 (PE = housing)
3 to 9 conductors
7
Rated short-time withstand current Icw (1s)
Up to 2.5 kA
50 kA
6
Rated peak withstand current Ipk
Up to 15.3 kA
105 kA
5
Rated current InA
40 A to 160 A
1,800 A to 7,000 A
4
Degree of protection
IP54, IP55
IP00
3
Rated operational voltage Ue
400 V AC
1,000 V AC
2
Rated insulation voltage Ui
400 V AC
1,000 V AC
1

התועלת שלך

  • בטיחות לאנשים ולצמחים

  • באמצעות אימות תכנון עם בדיקות לפי

  • IEC 61439-2

  • בטיחות אישית ומפעל במקרה של קשתות באמצעות בדיקות לפי IEC/TR 61641

  • גמישות גבוהה הודות לעיצוב מודולרי חדשני

קבצים להורדה

הורד עכשיו

CHECKLIST

IEC 61439

Project Checklist

PARTNERSHIP

SIVACON S8

Technology Partner

SII ORG

License to mark SIVACON S8 with the "Standard Mark"

IEEE ORG

License to mark SIVACON S8 with the "Quality Mark"

Anchor 1
Anchor 1
bottom of page